Online UPS Three Phase

TECHNICAL SPECIFICATIONS – FOR Online UPS Three Phase

CONFIGURATION

True ON – LINE Double Conversion UPS SYSTEMS with Pulse width modulation (PWM) Technology using IGBT Inverter.

RECTIFIER TYPE

Full Wave (Shall Fully meet the specified Input Power requirements)

INPUT VOLTAGE RANGE

415V : – 15% / + 10%

OUTPUT VOLTAGE

400V ± 1%

INPUT FREQUENCY

47Hz - 53Hz

SYSTEM DC VOLT

240VDC

INVERSION TECHNOLOGY

Microprocessor Controlled, Pulse width modulation with Instantaneous Sine Wave Control using IGBT.

INVERTER OUTPUT

(Output Galvanic Isolation through Double winding Isolation Transformer at Output of Inverter shall be part of UPS Design).

LOAD POWER FACTOR

0.8 to lag to Unity

REGULATION

For Balanced Load ± 1% For 100% Unbalanced Load ± 2%

FREQUENCY

50Hz ± 0.5%

WAVE FORM

True Sine Wave

TOTAL HARMONIC DISTORTION

Less Than 5%

OVERLOAD CAPACITY

Inverse Time Characteristic. 125% for 10 Minutes 150% for 1 Minutes

EFFICIENCY

1. Converter - 90%

2. Inverter - 85%

3. Overall - 80% (Full Load)

OPERATING TEMPERATURE

0 to 45 Degrees centigrades on Full Load

CREAST FACTOR

3 : 1

RELATIVE HUMIDITY

95% at 35 Degree Centigrade non – condensing.

CHARGER

Built in solid state Automatic float - cum - boost charger with constant current constant voltage mode of charging along with current limiting features. Ripple in DC shall not exceed 2% when battery is disconnected.

PROTECTION (INBUILT)

a. Output Under Voltage

b. Output Over Voltage

c. Output Overload

d. Output Short Circuit

e. HRC Fuses, Output & Battery

f. Battery Low trip

g. Battery Charging Current Limit.

INDICATIONS

1. Mains On

2. Inverter On,

3. U.P.S. on Battery

4. Load on U.P.S.

5. Battery Low

METERING

1. Output AC Volt.

2. Output DC Volt.